Part Number |
Torque |
Control Type |
Control Input |
Input Impedance |
Position Feedback |
Running Time (Motor) |
CAD |
Revit |
---|---|---|---|---|---|---|---|---|
AMB24-3-T N4 | N/A minimum 160 in·lbminimum 18 N·m | N/A On/Off, Floating Point | N/A On/Off, Floating Point | N/A 600 Ω | N/A | N/A 95 seconds constant, independent of load |
N/A ![]() |
N/A ![]() |
AMB24-3-T N4H | N/A minimum 160 in·lbminimum 18 N·m | N/A On/Off, Floating Point | N/A On/Off, Floating Point | N/A 600 Ω | N/A | N/A 95 seconds constant, independent of load |
N/A ![]() |
N/A ![]() |
AMB24-SR-T N4 | N/A minimum 160 in·lbminimum 18 N·m | N/A Modulating | N/A 2-10 VDC | N/A 100 kΩ for 2 to 10 VDC (0.1 mA), 500 Ω for 4 to 20 mA | N/A 2-10 VDC Feedback | N/A 95 seconds constant, independent of load |
N/A ![]() |
N/A ![]() |
AMB24-SR-T N4H | N/A minimum 160 in·lbminimum 18 N·m | N/A Modulating | N/A 2-10 VDC | N/A 100 kΩ for 2 to 10 VDC (0.1 mA), 500 Ω for 4 to 20 mA | N/A 2-10 VDC Feedback | N/A 95 seconds constant, independent of load |
N/A ![]() |
N/A ![]() |
AMX24-MFT-T N4 | N/A minimum 160 in·lbminimum 18 N·m | N/A Modulating | N/A MFT | N/A 100 kΩ for 2 to 10 VDC (0.1 mA), 500 Ω for 4 to 20 mA, 1500 Ω for PWM, on/off and floating point | N/A 2-10 VDC Feedback | N/A 90-350 seconds constant, independent of load (150) |
N/A ![]() |
N/A ![]() |
AMX24-MFT-T N4H | N/A minimum 160 in·lbminimum 18 N·m | N/A Modulating | N/A MFT | N/A 100 kΩ for 2 to 10 VDC (0.1 mA), 500 Ω for 4 to 20 mA, 1500 Ω for PWM, on/off and floating point | N/A 2-10 VDC Feedback | N/A 90-350 seconds constant, independent of load (150) |
N/A ![]() |
N/A ![]() |