AM Series (180 in-lb)
Damp.Rotary, 180in-lb, LON, 24V
Unit of Measure

Specifications

Product Type

N/A Damper Actuator

Actuator Type

N/A Non-Spring Return

Object name

N/A AMX24-LON

TYPECODE

N/A AM6501C1000

Application Type

N/A Air

Fail-Safe

N/A Non-Spring

Torque

N/A minimum 180 in·lbminimum 20 N·m

Control Type

N/A LON

Control Input

N/A LON

Position Feedback

N/A Sensor

Running Time (Motor)

N/A 150 seconds constant, independent of load

Power Supply

N/A 24 VAC ±20%, 50/60 Hz, 24 VDC ±10%

Power Consumption

N/A Running: 3.5 W, Holding: 1.3 W

Transformer Sizing

N/A 6 VA (class 2 power source)

Electrical Connection

N/A 3 ft, 18 GA plenum rated cable with 1/2" conduit connector, 10 ft (3m) and 15 ft (5m) avail.

Overload Protection

N/A Electronic throughout 0º to 95º rotation

Shaft Diameter

N/A Standard: 1/2" to 1.05" round, centers on 1/2" and 3/4" with insert, 1.05 without insert

Angle of Rotation

N/A max. 95º, adjustable with mechanical stop

Direction of Rotation (Motor)

N/A reversible with switch

Position Indication

N/A Reflective visual indicator (snap on)

Manual Override

N/A External push button

Humidity

N/A 5 to 95% RH non condensing (EN 60730-1)

Ambient Temperature

N/A -22 to +122 ºF-30 to +50 ºC

Storage Temperature

N/A -40 to +176 ºF-40 to +80 ºC

Noise Level

N/A max. 45 dB (A)

Housing

N/A NEMA 2, IP54, UL Enclosure Type 2

Agency Listing

N/A cULus acc. to UL60730-1A/-2-14, CAN/CSA E60730-1:02, CE acc. to 2004/108/EEC and 2006/95/EC

Servicing

N/A Maintenance Free

Quality Standards

N/A ISO 9001

Weight

N/A 1.5 lb1.18 kg

Application

N/A Direct coupled actuators for direct link to LonWorks network. Actuators are easily installed by direct shaft mounting on air dampers in ventilation and air conditioning systems. Actuator can be controlled by any compatible LON system.
For proportional modulation of dampers in HVAC systems. Actuator sizing should be done in accordance with the damper manufacturer’s specifications.
The actuator is mounted directly to a damper shaft up to 1.05” in diameter by means of its universal clamp, 1/2” self-centered default. A crank arm and several mounting brackets are available for applications where the actuator cannot be direct coupled to the damper shaft.