CAD (0)
  • Cart is empty
AH Linear Series (101 lbf)
Damp.Linear, 101lbf, On/Off/Float, 120V
Unit of Measure

Specifications

Product Type

N/A Damper Actuator

Actuator Type

N/A Non-Spring Return

Object name

N/A AHX120-3-100

TYPECODE

N/A AH0600A1000

Application Type

N/A Air

Fail-Safe

N/A Non-Spring

Torque

N/A 101 lb·ft450 N·m

Control Type

N/A On/Off, Floating Point

Control Input

N/A On/Off, Floating Point

Input Impedance

N/A 600 Ω

Position Feedback

N/A No Feedback

Running Time (Motor)

N/A 150 per 4 inches (100mm)

Power Supply

N/A 120 to 240 v 50/60 Hz

Power Consumption

N/A Running: 2.5 W, Holding: 0.5 W

Transformer Sizing

N/A 4.5 VA (class 2 power source)

Electrical Connection

N/A 3 ft, 18 GA applicance rated cable with 1/2" conduit connector, 10 ft (3m) and 15 ft (5m) avail.

Overload Protection

N/A electronic throughout full stroke

Direction of Rotation (Motor)

N/A reversible with switch

Manual Override

N/A External push button

Humidity

N/A 5 to 95% RH non condensing (EN 60730-1)

Ambient Temperature

N/A -22 to +122 ºF-30 to +50 ºC

Storage Temperature

N/A -40 to +176 ºF-40 to +80 ºC

Noise Level

N/A max. 35 dB (A)

Housing

N/A NEMA 2, IP54, UL enclosure type 2

Agency Listing

N/A cULus acc. to UL60730-1A/-2-14, CAN/CSA E60730-1:02, CE acc. to 2004/108/EEC and 2006/95/EC

Servicing

N/A Maintenance Free

Quality Standards

N/A ISO 9001

Weight

N/A 2.60 lb1.18 kg

Application

N/A For on/off and floating point control of dampers in HVAC systems. Actuator sizing should be done in accordance with the damper manufacturer’s specifications.