CAD (0)
  • Cart is empty
Globe Valve,4",2 Way,170 Cv,w/ Electronic Fail-Safe,24V,MFT
Unit of Measure

Specifications

TYPECODE

N/A G6JGC+AVKB24-MFT

Fail-Safe

N/A Electronic Fail-Safe

Control Type

N/A MFT (Configurable)

Input Impedance

N/A 100 k Ω for 2 to 10 VDC (0.1 mA), 500 Ω for 4 to 20 mA, 1500 Ω for PWM, floating point and On/Off

Position Feedback

N/A 2 to 10 VDC

Power Consumption

N/A 5 W ,2 W

Transformer Sizing

N/A 9.5 VA (class 2 power source)

Electrical Connection

N/A 3ft [1m], 18 GA plenum rated cable with 1/2" conduit connector protected NEMA 2 (IP54)

Overload Protection

N/A electronic throughout full stroke

Position Indication

N/A stroke indicator on bracket

Manual Override

N/A 5 mm hex crank (3/16" Allen), supplied

Humidity

N/A 5 to 95% RH non-condensing

Ambient Temperature

N/A -22°F to 122°F [-30°C to 50°C] -22 to 122 ºF-30 to 50 ºC

Storage Temperature

N/A -40°F to 176°F [-40°C to 80°C] -40 to 176 ºF-40 to 80 ºC

Noise Level

N/A <60 dB (A)

Housing

N/A NEMA 2, IP54, UL Enclosure Type 2

Servicing

N/A Repack/Rebuild kits available

Cv Rating

N/A 170

Flow Characteristic

N/A equal percentage

Service

N/A chilled or hot water, up to 60% glycol, steam

Action

N/A stem up - open A to AB

End Fitting

N/A 125 lb flanged

Leakage

N/A ANSI Class III

Rangeability

N/A 98:1

Valve Trim

N/A Bronze

Running Time (Motor)

N/A 90 sec (default), Optional (90 or 150 sec)

Valve

N/A G6100C

Actuator

N/A AVKB24-MFT

Application Type

N/A Water

Running Time (Fail-Safe)

N/A 35 sec

Agency Listing

N/A cULus acc. to UL60730-1A/-2-14, CAN/CSA E60730-1:02, CE acc. to 2004/108/EC and 2006/95/EC

Quality Standard

N/A ISO 9001

Weight

N/A 56.7 kg125 lb

Flow Pattern

N/A 2-Way

Media Temp Range (Water)

N/A 32 to 338 ºF0 to 138 ºC

Power Supply Type

N/A AC/DC 24 V