CAD (0)
  • Cart is empty
Fire&Smoke Actuator, 230 VAC, 70inlb, 1m Cable
Minimum Torque at 350?F
Unit of Measure

Specifications

Object name

N/A FSNF230 US

Application Type

N/A Fire and Smoke

Actuator Type

N/A Spring Return

Fail-Safe

N/A Spring

Minimum Torque

N/A 7.8 N·m70 lb·in

Control Type

N/A On/Off

Control Input

N/A On/Off

Running Time (Motor)

N/A 15 seconds

Running Time (Spring)

N/A 15 seconds

Power Supply

N/A 230 VAC ±10%, 50/60 Hz

Power Consumption

N/A Run 23 VA, Hold 9 VA, End stop 58 VA, 0.25 A slow blow fuse

Transformer Sizing

N/A 0 V·A

Electrical Connection

N/A 3 ft, 18 GA, 3 color coded leads

Overload Protection

N/A Electronic throughout 0º to 95º rotation

Shaft Diameter

N/A Rnd 1/2" to 1.05" Sq 1/2" Optional 3/8"-3/4" K4

Angle of Rotation

N/A 95° (Limiter available.)

Direction of Rotation (Fail-Safe)

N/A Reversible with CW/CCW mounting

Position Indication

N/A Visual (0° is spring return position)

Humidity

N/A 5 to 95% RH non-condensing

Ambient Temperature

N/A 32 to 122 ºF0 to 50 ºC

Ambient Temperature (safety for 1/2 hour)

N/A 350 ºF121 ºC177 ºC

Storage Temperature

N/A -40 to +176 ºF-40 to +80 ºC

Noise Level

N/A Inaudible holding, running < 45 dB (A) spring < 62 dB (A)

Housing

N/A NEMA type 1/IP40 (with flex conduit)

Agency Listing

N/A cULus listed to UL873 and CAN/CSA C22.2 No. 24

Servicing

N/A None

Quality Standards

N/A ISO 9001, 5-year warranty

Weight

N/A 6.6 lb3.10 kg

ETIM

Product Type

N/A Fire and Smoke

Application

N/A The type FSLF spring-return actuator is intended for the operation of smoke and combination fire and smoke dampers in ventiliation and air-conditioning systems. The actuator will meet requirements of UL555 and UL555S when tested as an assembly with the damper and will meet requirements of UBC for 15 second opening and closing.
Square footage of damper operated will depend on make and model and the temperature required.